1801 R0 XI.M1: Difference between revisions
en>Monica Hurley (Created page with "{{DISPLAYTITLE:XI.M1 (NUREG-1801 R0)}} Return to AMP Table '''XI.M1 ASME SECTION XI INSERVICE INSPECTION, SUBSECTIONS IWB, IWC, AND IWD''' '''Program Description''' The Code of Federal Regulations, [https://www.nrc.gov/reading-rm/doc-collections/cfr/part050/part050-0055a.html 10 CFR 50.55a], imposes the inservice inspection (ISI) requirements of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel (B&PV) Code,...") |
(Revision 0; Reviewed by Garry Young) |
||
| (One intermediate revision by the same user not shown) | |||
| Line 3: | Line 3: | ||
'''XI.M1 ASME SECTION XI INSERVICE INSPECTION, SUBSECTIONS IWB, IWC, AND IWD''' | '''XI.M1 ASME SECTION XI INSERVICE INSPECTION, SUBSECTIONS IWB, IWC, AND IWD''' | ||
'''Program Description''' | '''Program Description''' | ||
Latest revision as of 19:19, 4 October 2024
XI.M1 ASME SECTION XI INSERVICE INSPECTION, SUBSECTIONS IWB, IWC, AND IWD
Program Description
The Code of Federal Regulations, 10 CFR 50.55a, imposes the inservice inspection (ISI) requirements of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel (B&PV) Code, Section XI, for Class 1, 2, and 3 pressure-retaining components and their integral attachments in light-water cooled power plants. Inspection, repair, and replacement of these components are covered in Subsections IWB, IWC, and IWD, respectively, in the 1995 edition through the 1996 addenda. The program generally includes periodic visual, surface, and/or volumetric examination and leakage test of all Class 1, 2, and 3 pressure-retaining components and their integral attachments.
The ASME Section Xl inservice inspection program in accordance with Subsections IWB, IWC, or IWD has been shown to be generally effective in managing aging effects in Class 1, 2, or 3 components and their integral attachments in light-water cooled power plants. However, in certain cases, the ASME inservice inspection program is to be augmented to manage effects of aging for license renewal and is so identified in the GALL report.
Evaluation and Technical Basis
- 1. Scope of Program: The ASME Section Xl program provides the requirements for ISI, repair, and replacement. The components within the scope of the program are specified in Subsections IWB-1 100, IWC-1 100, and IWD-1 100 for Class 1, 2, and 3 components, respectively, and include all pressure-retaining components and their integral attachments in light-water cooled power plants. The components described in Subsections IWB-1220, IWC-1220, and IWD-1 220 are exempt from the examination requirements of Subsections IWB-2500, IWC-2500, and IWD-2500.
- 2. Preventive Actions: The ASME Section XI does not provide guidance on methods to mitigate degradation.
- 3. Parameters Monitored/Inspected: The ASME Section XI ISI program detects degradation of components by using the examination and inspection requirements specified in ASME Section XI Tables IWB-2500-1, IWC-2500-1, or IWD-2500-1, respectively, for Class 1, 2, or 3 components.
- 4. Detection of Aging Effects: The extent and schedule of the inspection and test techniques prescribed by the program are designed to maintain structural integrity and ensure that aging effects will be discovered and repaired before the loss of intended function of the component. Inspection can reveal crack initiation and growth; loss of material due to corrosion; leakage of coolant; and indications of degradation due to wear or stress relaxation, such as verification of clearances, settings, physical displacements, loose or missing parts, debris, wear, erosion, or loss of integrity at bolted or welded connections.
- Components are examined and tested as specified in Tables IWB-2500-1, IWC-2500-1, and IWD-2500-1, respectively, for Class 1, 2, and 3 components. The tables specify the extent and schedule of the inspection and examination methods for the components of the pressure-retaining boundaries. Alternative approved methods that meet the requirements of IWA-2240 are also specified in these tables.
- The program uses three types of examination - visual, surface, and volumetric - in accordance with the general requirements of Subsection IWA-2000. Visual VT-1 examination detects discontinuities and imperfections, such as cracks, corrosion, wear, or erosion, on the surface of components. Visual VT-2 examination detects evidence of leakage from pressure-retaining components, as required during the system pressure test. Visual VT-3 examination (a) determines the general mechanical and structural condition of components and their supports by verifying parameters, such as clearances, settings, and physical displacements; (b) detects discontinuities and imperfections, such as loss of integrity at bolted or welded connections, loose or missing parts, debris, corrosion, wear, or erosion; and (c) observes conditions that could affect operability or functional adequacy of constant-load and spring-type components and supports.
- Surface examination uses magnetic particle, liquid penetrant, or eddy current examinations to indicate the presence of surface discontinuities and flaws.
- Volumetric examination uses radiographic, ultrasonic, or eddy current examinations to indicate the presence of discontinuities or flaws throughout the volume of material included in the inspection program.
- For BWRs, the nondestructive examination (NDE) techniques appropriate for inspection of vessel internals and their implementation needs, including the uncertainties inherent in delivering and executing and NDE technique in a boiling water reactor (BWR), are included in the approved boiling water reactor vessel and intemals project (BWRVIP)-03. Also, an applicant may use the guidelines of the approved BWRVIP-62 for inspection relief for vessel internal components with hydrogen water chemistry.
- The ASME Section XI examination categories used in this report are given below. These examination categories are based on the 1989 edition of Section Xl of the ASME Code; any differences in the examination categories in the 1995 edition through the 1996 addenda from those in the 1989 edition are identified.
- Class 1 Components, Table IWB-2500-1
- Examination category B-B, for pressure-retaining welds in vessels other than reactor vessels: This category specifies volumetric examination of circumferential and longitudinal shell-to-head welds and circumferential and meridional head welds in pressurizers, and circumferential and meridional head welds and tubesheet-to-head welds in steam generators (primary side). The welds selected during the first inspection interval are reexamined during successive inspection intervals.
- Examination category B-D, for full penetration welds of nozzles in reactor vessels, pressurizers, steam generators (primary side), and heat exchangers (primary side): This category specifies volumetric examination of all nozzle-to-vessel welds and the nozzle inside radius. Examination category B-E, for pressure-retaining partial penetration welds in vessels. This category specifies visual VT-2 examination of partial penetration welds in nozzles and penetrations in reactor vessels and pressurizers during the hydrostatic test. In the 1995 edition of the ASME Code, examination category B-E is covered under examination category B-P.
- Examination category B-F, for pressure-retaining dissimilar metal welds in reactor vessels, pressurizers, steam generators, heat exchangers, and piping: This category specifies volumetric examination of the inside diameter (ID) region and surface examination of the outside diameter (OD) surface for all nozzle-to-safe end butt welds of nominal pipe size (NPS) 4 in. or larger. Only surface examination is conducted for all butt welds less than NPS 4 in. and for all nozzle-to-safe end socket welds. Examinations are required for each safe end weld in each loop and connecting branch of the reactor coolant system. In the 1995 edition of the ASME Code, examination category B-F for piping is covered under examination category B-J for all pressure-retaining welds in piping.
- Examination category B-G-1 for pressure-retaining bolting greater than 2 in. in diameter, and category B-G-2 for pressure-retaining bolting less than 2 in. in diameter in reactor vessels, pressurizers, steam generators, heat exchangers, piping, pumps, and valves: Category B-G-1 specifies volumetric examination of studs in place, from the top of the nut to the bottom of the flange hole; and surface and volumetric examination of studs when removed; volumetric examination of flange threads; and visual VT-1 examination of the surfaces of nuts, washers, and bushings. Category B-G-2 specifies visual VT-1 examination of the surfaces of nuts, washers, and bushings. For heat exchangers, piping, pumps, and valves, examinations are limited to components selected for examination under examination categories B-B, B-J, B-L-2, and B-M-2.
- Examination category B-H for integral attachments for vessels: This category specifies volumetric or surface examination of essentially 100% of the length of the attachment weld at each attachment subject to examination.
- Examination category B-J for pressure-retaining welds in piping: This category specifies volumetric examination of the ID region and surface examination of the OD for circumferential and longitudinal welds in each pipe or branch run NPS 4 in. or larger. Surface examination is conducted for circumferential and longitudinal welds in each pipe or branch run less than NPS 4 in. and for all socket welds. The pipe welds selected during the first inspection interval are reexamined during each successive inspection interval.
- Examination category B-L-1, for pressure-retaining welds in pump casing, and category B-L-2, for pump casing: Category B-L-1 specifies volumetric examination of all welds, and category B-L-2 specifies visual VT-3 examination of internal surfaces of the pump casing. All welds from at least one pump in each group of pumps performing similar functions in the system (such as recirculating coolant pumps) are inspected during each inspection interval. Visual examination is required only when the pump is disassembled for maintenance, repair, or volumetric examination, but one pump in a particular group of pumps is visually examined at least once during the inspection interval.
- Examination category B-M-1, for pressure-retaining welds in valve bodies and category B-M-2, for valve bodies: Category B-M-1 specifies volumetric examination for all welds in valve bodies NPS 4 in. or larger, and surface examination of OD surfaces for all welds in valve bodies less than NPS 4 in. Category B-M-2 specifies visual VT-3 examination of internal surfaces of valve bodies. All welds from at least one valve in each group of valves that are of the same size, construction design (such as globe, gate, or check valves), and manufacturing method, and that perform similar functions in the system (such as the containment isolation valve) are inspected during each inspection interval. Visual examination is required only when the valve is disassembled for maintenance, repair, or volumetric examination, but one valve in a particular group of valves is visually examined at least once during the inspection interval.
- Examination category B-N-1, for the interior of reactor vessels: Category B-N-1 specifies visual VT-3 examination of interior surfaces that are made accessible for examination by removal of components during normal refueling outages. Examination category B-N-2, for integrally welded core support structures and interior attachments to reactor vessels: Category B-N-2 specifies visual VT-1 examination of all accessible welds in interior attachments within the beltline region; visual VT-3 examination of all accessible welds in interior attachments beyond the beltline region; and, for BWRs, visual VT-3 examination of all accessible surfaces in the core support structure.
- Examination category B-N-3, which is applicable to pressurized water reactors (PWRs), for removable core support structures: Category B-N-3 specifies visual VT-3 examination of all accessible surfaces of reactor core support structures that can be removed from the reactor vessel.
- Examination category B-0, for pressure-retaining welds in control rod housing: This category specifies volumetric or surface examination of the control rod drive (CRD) housing welds, including the weld buttering.
- Examination category B-P, for all pressure-retaining components: This category specifies visual VT-2 examination of all pressure-retaining boundary components during the system leakage test and hydrostatic test (IWA-5000 and IWB-5000). The pressure-retaining boundary during the system leakage test corresponds to the reactor coolant system boundary, with all valves in the normal position, which is required for normal reactor operation startup. However, VT-2 visual examination extends to and includes the second closed valve at the boundary extremity. The 1995 edition of the ASME Code eliminates the hydrostatic test because equivalent results are obtained from the leakage test. The pressure-retaining boundary for the hydrostatic test (1989 edition) and system leakage test (1995 edition) conducted at or near the end of each inspection interval extends to all Class 1 pressure-retaining components within the system boundary.
- Class 2 Components, Table IWC-2500-1
- Examination category C-A, for pressure-retaining welds in pressure vessels: This category specifies volumetric examination of circumferential welds at gross structural discontinuities, such as junctions between shells of different thickness or cylindrical shell-to-conical shell junctions, and head-to-shell, shell (or head)-to-flange, and tubesheet-to-shell welds.
- Examination category C-F- 1, for pressure-retaining welds in austenitic stainless steel or high-alloy piping: This category specifies, for circumferential and longitudinal welds in each pipe or branch run NPS 4 in. or larger, volumetric and surface examination of the ID region, and surface examination of the OD surface for piping welds Ž_3/8 in. nominal wall thickness for piping >NPS 4 in. or for piping welds >1/5 in. nominal wall thickness for piping >_NPS 2 in. and --NPS 4 in. Surface examination is conducted for circumferential and longitudinal welds in pipe branch connections of branch piping Ž_NPS 2 in. and for socket welds.
- Examination category C-G, for all pressure-retaining welds in pumps and valves: This category specifies surface examination of either the inside or outside surface of all welds in the pump casing and valve body. In a group of multiple pumps or valves of similar design, size, function, and service in a system, examination of only one pump or one valve among each group of multiple pumps or valves is required to detect the loss of intended function of the pump or valve.
- Examination category C-H, for all pressure-retaining components: This category specifies visual VT-2 examination during system pressure tests (IWA-5000 and IWC-5000) of all pressure-retaining boundary components. The pressure-retaining boundary includes only those portions of the system required to operate or support the safety function, up to and including the first normally closed valve (including a safety or relief valve) or valve capable of automatic closure when the safety function is required. The 1995 edition of the ASME Code eliminates the hydrostatic test because equivalent results are obtained from the leakage test.
- Class 3 Components, Table IWD-2500-1
- Examination category D-A (1989 edition), for systems in support of reactor shutdown function, and category D-B (1989 edition), for systems in support of emergency core cooling, containment heat removal, atmosphere cleanup, and reactor residual heat removal: Categories D-A and D-B specify visual VT-2 examination during system pressure tests (IWA-5000 and IWD-5000) of all pressure-retaining boundary components. The pressure retaining boundary extends up to and includes the first normally closed valve or valve capable of automatic closure as required to perform the safety-related system function. Examination categories D-A and D-B, from the 1989 edition of the ASME Code, have been combined into examination category D-B for all pressure-retaining components in the 1995 edition of the ASME Code.
- 5. Monitoring and Trending: For Class 1, 2, or 3 components, the inspection schedule of IWB-2400, IWC-2400, or IWD-2400, respectively, and the extent and frequency of IWB 2500-1, IWC-2500-1, or IWD-2500-1, respectively, provides for timely detection of degradation. The sequence of component examinations established during the first inspection interval is repeated during each successive inspection interval, to the extent practical. If flaw indications or relevant conditions of degradation are evaluated in accordance with IWB-31 00 or IWC-31 00, and the component is qualified as acceptable for continued service, the areas containing such flaw indications and relevant conditions are reexamined during the next three inspection periods of IWB-241 0 for Class 1 components and for the next inspection period of IWC-2410 for Class 2 components. Examinations that reveal indications that exceed the acceptance standards described below are extended to include additional examinations in accordance with IWB-2430, IWC-2430, or IWD-2430 (1995 edition) for Class 1, 2, or, 3 components, respectively.
- 6. Acceptance Criteria: Any indication or relevant conditions of degradation detected are evaluated in accordance with IWB-3000, IWC-3000, or IWD-3000, for Class 1, 2, or 3 components, respectively. Examination results are evaluated in accordance with IWB-31 00 or IWC-3100 by comparing the results with the acceptance standards of IWB-3400 and IWB-3500 or IWC-3400 and IWC-3500, respectively, for Class 1 or Class 2 and 3 components. Flaws that exceed the size of allowable flaws, as defined in IWB-3500 or IWC 3500, are evaluated by using the analytical procedures of IWB-3600 or IWC-3600, respectively, for Class 1 or Class 2 and 3 components. Approved BWRVIP-14, BWRVIP-59, and BWRVIP-60 documents provide guidelines for evaluation of crack growth in stainless steels, nickel alloys, and low-alloy steels, respectively.
- 7. Corrective Actions: For Class 1, 2, and 3, respectively, repair is in conformance with IWB 4000, IWC-4000, and IWD-4000, and replacement according to IWB-7000, IWC-7000, and IWD-7000. Approved BWRVIP-44 and BWRVIP-45 documents, respectively, provide guidelines for weld repair of nickel alloys and for weldability of irradiated structural components. As discussed in the appendix to this report, the staff finds the requirements of 10 CFR Part 50, Appendix B, acceptable in addressing corrective actions.
- 8. Confirmation Process: Site quality assurance (QA) procedures, review and approval processes, and administrative controls are implemented in accordance with the requirements of 10 CFR Part 50, Appendix B. As discussed in the appendix to this report, the staff finds the requirements of 10 CFR Part 50, Appendix B, acceptable in addressing the confirmation process and administrative controls.
- 9. Administrative Controls: See Item 8, above.
- 10. Operating Experience: Because the ASME Code is a consensus document that has been widely used over a long period, it has been shown to be generally effective in managing aging effects in Class 1, 2, and 3 components and their integral attachments in light-water cooled power plants (see Chapter I of the GALL report, Vol. 2).
- Some specific examples of operating experience of component degradation are as follows:
- BWR: Cracking due to intergranular stress corrosion cracking (IGSCC) has occurred in small- and large-diameter BWR piping made of austenitic stainless steels and nickel alloys. The IGSCC has also occurred in a number of vessel internal components, such as core shrouds, access hole covers, top guides, and core spray spargers (US NRC IE Bulletin 80-13, US NRC Information Notice [IN 95-17], US NRC Generic Letter [GL 94-03], and NUREG-1544). Crack initiation and growth due to thermal and mechanical loading have occurred in high pressure coolant injection (HPCI) piping (US NRC IN 89-80) and instrument lines US NRC Licensee Event Report [LER] 50-249/99-003-1). Jet pump BWRs are designed with access holes in the shroud support plate at the bottom of the annulus between the core shroud and the reactor vessel wall. These holes are used for access during construction and are subsequently closed by welding a plate over the hole. Both circumferential (US NRC IN 88-03) and radial cracking (US NRC IN 92-57) have been observed in access hole covers. Failure of the isolation condenser tube bundles due to thermal fatigue and transgranular stress corrosion cracking (TGSCC) due to leaky valves has also occurred (US NRC LER 50-219/98 014).
- PWR Primary System: Although the primary pressure boundary piping of PWRs has generally not been found to be affected by SCC because of low dissolved oxygen levels and control of primary water chemistry, SCC has occurred in safety injection lines (US NRC IN 97-19 and 84-18), charging pump casing cladding (US NRC IN 80-38 and 94-63), instrument nozzles in safety injection tanks (US NRC IN 91-05), CRD seal housing (US NRC Inspection Report 50-255/99012), and safety-related stainless steel (SS) piping systems that contain oxygenated, stagnant, or essentially stagnant borated coolant (US NRC IN 97-19). Cracking has occurred in SS baffle former bolts in a number of foreign plants (US NRC IN 98-11) and has now been observed in plants in the United States. Crack initiation and growth due to thermal and mechanical loading has occurred in high-pressure injection and safety injection piping (US NRC IN 97-46 and US NRC BL 88-08).
- PWR Secondary System: Steam generator tubes have experienced outside diameter stress corrosion cracking (ODSCC), intergranular attack (IGA), wastage, and pitting (US NRC IN 97-88). Carbon steel support plates in steam generators have experienced general corrosion. Steam generator shells have experienced pitting and stress corrosion cracking (US NRC INs 82-37, 85-65, and 90-04).
References
10 CFR 50.55a, Codes and Standards, Office of the Federal Register, National Archives and Records Administration, 2000.
ASME Section XI, Rules for Inservice Inspection of Nuclear Power Plant Components, ASME Boiler and Pressure Vessel Code, 1989 edition, American Society of Mechanical Engineers, New York, NY.
ASME Section XI, Rules for Inservice Inspection of Nuclear Power Plant Components, ASME Boiler and Pressure Vessel Code, 1995 edition through the 1996 Addenda, American Society of Mechanical Engineers, New York, NY.
BWRVIP-03, BWR Vessel and Internals Project, Reactor Pressure Vessel and Internals Examination Guidelines, (EPRI TR-105696 R1, March 30, 1999)(Archived), Final Safety Evaluation Report by the Office of Nuclear Reactor Regulation for BWRVIP-03, July 15, 1999.
BWRVIP-14, Evaluation of Crack Growth in BWR Stainless Steel RPV Internals, (EPRI TR-105873, July 11, 2000)(Archived), Final Safety Evaluation Report by the Office of Nuclear Reactor Regulation for BWRVIP-14, December 3, 1999.
BWRVIP-44, Underwater Weld Repair of Nickel Alloy Reactor Vessel Internals, (EPRI TR-108708, April 3,2000)(Archived), Final Safety Evaluation Report by the Office of Nuclear Reactor Regulation for BWRVIP-44, June 9, 1999.
BWRVIP-45, Weldability of Irradiated L WR Structural Components, (EPRI TR-108707), BWRVIP and Electric Power Research Institute, Palo Alto, CA, June 14, 2000.
BWRVIP-59, Evaluation of Crack Growth in BWR Nickel-Base Austenitic Alloys in RPV Internals, (EPRI TR-108710)(Archived), BWRVIP and Electric Power Research Institute, Palo Alto, CA, March 24, 2000.
BWRVIP-60, BWR Vessel and Internals Project, Evaluation of Crack Growth in BWR Low Alloy Steel RPV Internals, (EPRI TR-108709, April 14, 2000)(Archived), Final Safety Evaluation Report by the Office of Nuclear Reactor Regulation for BWRVIP-60, July 8, 1999.
BWRVIP-62, BWR Vessel and Internals Project, Technical Basis for Inspection Relief for BWR Internal Components with Hydrogen Injection, (EPRI TR-108705), BWRVIP and Electric Power Research Institute, Palo Alto, CA, March 7, 2000. (Archived)
US NRC Bulletin 88-08, Thermal Stresses in Piping Connected to Reactor Coolant Systems, U.S. Nuclear Regulatory Commission, June 22, 1988; Supplement 1, June 24, 1988; Supplement 2, September 4, 1988; Supplement 3, April 4, 1989.
US NRC Generic Letter 94-03, Intergranular Stress Corrosion Cracking of Core Shrouds in Boiling Water Reactors, U.S. Nuclear Regulatory Commission, July 25, 1994.
US NRC IE Bulletin 80-13, Cracking in Core Spray Spargers, U.S. Nuclear Regulatory Commission, May 12, 1980.
US NRC Information Notice 80-38, Cracking in Charging Pump Casing Cladding, U.S. Nuclear Regulatory Commission, October 31, 1980.
US NRC Information Notice 82-37, Cracking in the Upper Shell to Transition Cone Girth Weld of a Steam Generator at an Operating PWR, U.S. Nuclear Regulatory Commission, September 16, 1982.
US NRC Information Notice 84-18, Stress Corrosion Cracking in PWR Systems, U.S. Nuclear Regulatory Commission, March 7, 1984.
US NRC Information Notice 85-65, Crack Growth in Steam Generator Girth Welds, U.S. Nuclear Regulatory Commission, July 31, 1985.
US NRC Information Notice 88-03, Cracks in Shroud Support Access Hole Cover Welds, U.S. Nuclear Regulatory Commission, February 2, 1988.
US NRC Information Notice 89-80, Potential for Water Hammer, Thermal Stratification, and Steam Binding in High-Pressure Coolant Injection Piping, U.S. Nuclear Regulatory Commission, December 1, 1989.
US NRC Information Notice 90-04, Cracking of the Upper Shell-to-Transition Cone Girth Welds in Steam Generators, U.S. Nuclear Regulatory Commission, January 26, 1990.
US NRC Information Notice 91-05, Intergranular Stress Corrosion Cracking in Pressurized Water Reactor Safety Injection Accumulator Nozzles, U.S. Nuclear Regulatory Commission, January 30, 1991.
US NRC Information Notice 92-57, Radial Cracking of Shroud Support Access Hole Cover Welds, U.S. Nuclear Regulatory Commission, August 11, 1992.
US NRC Information Notice 94-63, Boric Acid Corrosion of Charging Pump Casing Caused by Cladding Cracks, U.S. Nuclear Regulatory Commission, August 30, 1994.
US NRC Information Notice 95-17, Reactor Vessel Top Guide and Core Plate Cracking, U.S. Nuclear Regulatory Commission, March 10, 1995.
US NRC Information Notice 97-19, Safety Injection System Weld Flaw at Sequoyah Nuclear Power Plant, Unit 2, U.S. Nuclear Regulatory Commission, April 18, 1997.
US NRC Information Notice 97-46, Unisolable Crack in High-Pressure Injection Piping, U.S. Nuclear Regulatory Commission, July 9, 1997.
US NRC Information Notice 97-88, Experiences During Recent Steam Generator Inspections, U.S. Nuclear Regulatory Commission, December 16, 1997.
US NRC Information Notice 98-11, Cracking of Reactor Vessel Internal Baffle Former Bolts in Foreign Plants, U.S. Nuclear Regulatory Commission, March 25, 1998.
US NRC Inspection Report 50-255/99012, Palisades Inspection Report, Item E8.2, Licensee Event Report 50-255/99-004, Control Rod Drive Seal Housing Leaks and Crack Indications, U.S. Nuclear Regulatory Commission, January 12, 2000.
US NRC Licensee Event Report LER # 98-014-00, Failure of the Isolation Condenser Tube Bundles due to Thermal Stresses/Transgranular Stress Corrosion Cracking Caused by Leaky Valve, U.S. Nuclear Regulatory Commission, October 29, 1998.
US NRC Licensee Event Report LER # 99-003-01, Supplement to Reactor Recirculation B Loop, High Pressure Flow Element Venturi Instrument Line Steam Leakage Results in Unit 3 Shutdown Due to Fatigue Failure of Socket Welded Pipe Joint, U.S. Nuclear Regulatory Commission, August 30, 1999.