XI.M27 (NUREG-1801 R0)

From EPRI Nuclear LTO Wiki
Revision as of 19:26, 9 July 2024 by en>Monica Hurley (Created page with "{{DISPLAYTITLE:XI.M27 (NUREG-1801 R0)}} Return to AMP Table '''XI.M27 FIRE WATER SYSTEM''' '''Program Description''' This aging management program applies to water-based fire protection systems that consist of sprinklers, nozzles, fittings, valves, hydrants, hose stations, standpipes, water storage tanks, and aboveground and underground piping and components that are tested in accordance with the applicable National Fire Pro...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search

Return to AMP Table

XI.M27 FIRE WATER SYSTEM


Program Description

This aging management program applies to water-based fire protection systems that consist of sprinklers, nozzles, fittings, valves, hydrants, hose stations, standpipes, water storage tanks, and aboveground and underground piping and components that are tested in accordance with the applicable National Fire Protection Association (NFPA) codes and standards. Such testing assures the minimum functionality of the systems. Also, these systems are normally maintained at required operating pressure and monitored such that loss of system pressure is immediately detected and corrective actions initiated. In addition to NFPA codes and standards, which do not currently contain programs to manage aging, portions of the fire protection sprinkler system, which are not routinely subjected to flow, are to be subjected to full flow tests at the maximum design flow and pressure before the period of extended operation (and at not more than 5-year intervals thereafter). In addition, a sample of sprinkler heads is to be inspected by using the guidance of NFPA 25, Section 2.3.3.1. This NFPA section states that "where sprinklers have been in place for 50 years, they shall be replaced or representative samples from one or more sample areas shall be submitted to a recognized testing laboratory for field service testing." It also contains guidance to perform this sampling every 10 years after the initial field service testing. Finally, portions of fire protection suppression piping located aboveground and exposed to water are disassembled and visually inspected internally once every refueling outage. The purpose of the full flow testing and internal visual inspections is to ensure that corrosion, microbiological influenced corrosion (MIC), or biofouling aging effects are managed such that the system function is maintained.


Evaluation and Technical Basis

1. Scope of Program: The aging management program focuses on managing loss of material due to corrosion, MIC, or biofouling of carbon steel and cast-iron components in fire protection systems exposed to water. Hose station and standpipe are considered as piping in the AMP.
2. Preventive Actions: To ensure no significant corrosion, MIC, or biofouling has occurred in water-based fire protection systems, periodic flushing, system performance testing, and inspections are conducted.
3. Parameters Monitored/Inspected: Loss of material due to corrosion and biofouling could reduce wall thickness of the fire protection piping system and result in system failure. Therefore, the parameters monitored are the system's ability to maintain pressure and internal system corrosion conditions. The US NRC GL 89-13 recommends periodic flow testing of infrequently used loops of the fire water system at the maximum design flow to ensure that the system maintains its intended function.
4. Detection of Aging Effects: Fire protection system testing is performed to assure required pressures. Internal inspections of aboveground fire protection piping and the smaller diameter fire suppression piping are performed on system components (when they are disassembled) to identify evidence of loss of material due to corrosion. Repair and replacement actions are initiated as necessary. Continuous system pressure monitoring, periodic system flow testing performed, and internal inspections of aboveground piping are effective means to ensure that corrosion and biofouling are not occurring and the system's intended function is maintained. In addition, general requirements of existing fire protection programs include testing and maintenance of fire detection and suppression systems and surveillance procedures to ensure that fire detectors, as well as fire suppression systems and components, are operable.
Visual inspection of yard fire hydrants performed once every six months ensures timely detection of signs of degradation, such as corrosion. Fire hydrant hose hydrostatic tests, gasket inspections, and fire hydrant flow tests, performed annually, ensure that fire hydrants can perform their intended function and provide opportunities for degradation to be detected before a loss of intended function can occur.
Sprinkler systems are inspected once every refueling outage to ensure that signs of degradation, such as corrosion, are detected in a timely manner.
5. Monitoring and Trending: System discharge pressure is monitored continuously. Results of system performance testing are monitored and trended as specified by the NFPA codes and standards. Degradation identified by internal inspection is evaluated.
6. Acceptance Criteria: The acceptance criteria are (a) the ability of a fire protection system to maintain required pressure, (b) no unacceptable signs of degradation observed during visual assessment of internal system conditions, and (c) that no biofouling exists in the sprinkler systems that could cause corrosion in the sprinkler heads.
7. Corrective Actions: For fire water systems and components identified within scope that are subject to an aging management review for license renewal, the applicant is to expand the scope of the 10 CFR Part 50, Appendix B, program to include these in-scope systems and components to address corrective actions, confirmation process, and administrative controls for aging management during the period of extended operation. As discussed in the appendix to this report, the staff finds the requirements of 10 CFR Part 50, Appendix B, acceptable to address corrective actions, confirmation process, and administrative controls.
8. Confirmation Process: See Item 7, above.
9. Administrative Controls: See Item 7, above.
10. Operating Experience: Water-based fire protection systems designed, inspected, tested and maintained in accordance with the NFPA minimum standards have demonstrated reliable performance.


References

NFPA 25: Inspection, Testing and Maintenance of Water-Based Fire Protection Systems, 1998 Edition.

US NRC Generic Letter 89-13, Service Water System Problems Affecting Safety-Related Equipment, July 18, 1989.